Stilling wells - general notes
Installation in tanks containing one liquid and foam

• Drill an air circulation hole (max. Ø10 mm / 0.4¨) in the stilling well above the maximum level.
• Remove the burr from the hole.

Installation in tanks containing one liquid or more without foam

• Drill an air circulation hole (max. Ø10 mm / 0.4¨) in the stilling well above the maximum level.
• Drill 1 or more liquid circulation holes in the stilling well (if there is more than 1 liquid in the

tank).

i

These holes help the liquid to move freely between the stilling well and the tank.

• Remove the burr from the hole.

Stilling wells - reference point

We recommend that you attach a flat cruciform target at the bottom of the stilling well. It must
have a width of 1/3 of the internal diameter of the stilling well tube. This target is the limit of the
measuring range in the stilling well.

Figure 3-17: Reference point in the stilling well

a ≥ 1/3 × ШD