Edwards Signaling FSC Series User Manual
Page 97
Appendix B: Programming templates
FSC Series Technical Reference Manual
89
IDC 1 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000001
11 E1
Waterflow zone active
None
1
2
1 & 2
(1/3)13000001
21 EA
Trouble
None
1
2
1 & 2
(1/3)37300001
71 F1
Supervisory zone active
None
1
2
1 & 2
(1/3)20000001
31 E1
Monitor zone active
None
1
2
1 & 2
(1/3)40000001
5A EA
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.
IDC 2 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000002
12 E2
Waterflow zone active
None
1
2
1 & 2
(1/3)13000002
22 E2
Trouble
None
1
2
1 & 2
(1/3)37300002
72 F2
Supervisory zone active
None
1
2
1 & 2
(1/3)20000002
32 E2
Monitor zone active
None
1
2
1 & 2
(1/3)40000002
52 E2
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.