Selecting dialer options, Entering values for dialer options – Edwards Signaling FSC Series User Manual
Page 55
Chapter 4: Dialer programming
FSC Series Technical Reference Manual
47
To exit dialer program mode:
1. Remove the jumper from J3 (PRG).
The panel automatically resets after the jumper on J3 is removed.
Selecting dialer options
Use the Signal Silence & Drill and Remote Disconnect buttons to select dialer
options. Pressing Signal Silence & Drill selects the next option. Pressing Remote
Disconnect selects the previous option.
In the programming instructions that follow, when you see “select this option,”
press Signal Silence & Drill or Remote Disconnect until the option is displayed on
the LCD.
Entering values for dialer options
Use the Panel Silence, Walk Test, and Reset buttons to enter values for the
selected dialer option. Pressing Panel Silence selects the next value. Pressing
Walk Test selects the previous value. Pressing Reset enters the value.
In the programming instructions that follow, whenever you see “enter this value,”
use the Panel Silence or Walk Test buttons to select the value then press Reset.
When entering a set of numbers, pressing the Panel Silence and Walk Test
buttons increases or decreases the number. Pressing Reset enters the number
and positions the cursor at the next number. If the number doesn’t need to be
changed, press Reset to go to the next number.
SIGNAL
SILENCE
& DRILL
REMOTE
DISCON-
NECT
NEXT
OPTION
PREVIOUS
OPTION
PANEL
SILENCE
WALK
TEST
NEXT
OPTION
PREVIOUS
OPTION
RESET
ENTER