Setting idc 4/2 event activation code options – Edwards Signaling FSC Series User Manual
Page 65
Chapter 4: Dialer programming
FSC Series Technical Reference Manual
57
Option Description
Values
Wlk Tst CODE
Determines the 4/2 code that the dialer
transmits when the control panel is placed
in walk test mode
0 to 9, and A to F
Default: AF
Drill CODE
Determines the 4/2 code that the dialer
transmits when notification appliance
circuits are manually activated
0 to 9, and A to F
Default: AD
Signal Sil CODE
Determines the 4/2 code that the dialer
transmits when notification appliance
circuits are automatically or manually
silenced
0 to 9, and A to F
Default: AC
Panel Sil CODE
Determines the 4/2 code that the dialer
transmits when the control panel is
silenced
0 to 9, and A to F
Default: CA
Line 1 Trb CODE
Determines the 4/2 code that the dialer
transmits when the dialer detects a line cut
or ground fault on LINE 1
0 to 9, and A to F
Default: 68
Line 2 Trb CODE
Determines the 4/2 code that the dialer
transmits when the dialer detects a line cut
or ground fault on LINE 2
0 to 9, and A to F
Default: 6E
Program CODE
Determines the 4/2 code that the dialer
transmits when the control panel is placed
in program mode
0 to 9, and A to F
Default: C1
Delivery Trb CDE
Determines the 4/2 code that the dialer
transmits when the dialer transmits a
signal to an account and the account
doesn’t answer
0 to 9, and A to F
Default: 67
Disable CODE
Determines the 4/2 code that the dialer
transmits when the dialer is disabled
0 to 9, and A to F
Default: AE
CS Test CODE
Determines the 4/2 code that the dialer
transmits as the test signal when the
control panel is in the normal state
0 to 9, and A to F
Default: DF
Reset CODE
Determines the 4/2 code that the dialer
transmits when the control panel is reset
0 to 9, and A to F
Default: AB
Setting IDC 4/2 event activation code options
Table 22 lists the set of IDC 4/2 event activation code options and their default
values.
Review Table 22 and make changes as required. If you don’t need to make any
changes, go to “Setting NAC 4/2 event activation code options“ on page 58.