Edwards Signaling FSC Series User Manual
Page 50
Chapter 3: Panel programming
42
FSC Series Technical Reference Manual
Step Option
Values
LCD first line
ALARM
TROUBLE
SUP
POWER
DISABLE
LCD second line
WATERFLO
W
ANN TROUBL
E
BATT TROUBLE
GND FAULT
SERVICE DETECTOR
13
minutes
14
minutes
15
minutes
16
minutes
17
minutes
18
minutes
19
minutes
20
minutes
21
minute
22
minutes
23
minutes
24
minutes
25
minutes
26
minutes
27
minutes
28
minutes
29
minutes
30
minutes
24
NAC Silenceable [5]
No
Yes
(default)
1. = OFF, = ON.
[2] City tie NAC types can’t be silenced or disabled. To inhibit operation of city tie NAC types you must
press the control panel’s Remote Disconnect button.
[3] Class A notification appliance circuits are programmed in odd-even pairs. If you program either circuit as
Class A, NAC type and NAC silenceable values are automatically entered for both circuits.
[4] Does not turn off NACs activated by waterflow, waterflow-retard, waterflow/supervisory, and waterflow-
retard/supervisory zone types.
[5] Does not affect notification appliance circuits whose NAC Type option is set for City Tie or those
activated by a waterflow switch.