Appendix A: System calculations
FSC Series Technical Reference Manual
71
Notes
[1] The base panel standby and alarm currents consist of the main controller
board with no load other than the end-of-line resistors. In addition, the base
panel alarm current includes the IDC alarm current. Use these values for
base panel standby and alarm currents:
Control panel
Standby
Alarm
Three-zone
96 mA
180 mA
Five-zone
104 mA
224 mA
Ten-zone
128 mA
242 mA
[2] The maximum battery size that the panel can charge is 24 Ah (model 12V24A
or equivalent).
Battery space inside the control panel is limited. See Appendix D “Panel
specifications” on page 115 for more information.
[3] The IDC detector alarm current is included in the base panel alarm current.
For IDC detector standby current, enter the calculated total IDC standby
current from Form B or use these values:
Control panel
Total IDC standby current
Three-zone 9
mA
Five-zone 15
mA
Ten-zone 30
mA
[4] Standby time value: 24 or 60 hours.
[5] Alarm time values:
5 min = 0.083 hr
10 min = 0.167 hr
15 min = 0.250 hr
30 min = 0.500 hr
[6] Total standby current may not exceed 635 mA.