Setting system 4/2 event activation code
options
Table 21 lists the set of system 4/2 event activation code options and their
default values.
Review Table 21 and make changes as required. If you don’t need to make any
changes, go to “Setting IDC 4/2 event activation code options“ on page 57.
Table 21: System 4/2 event activation code options
Option Description
Values
Int Comm TR
CODE
Determines the 4/2 code that the dialer
transmits when the control panel and the
dialer are not communicating
0 to 9, and A to F
Default: AA
CS AB Test CODE Determines the 4/2 code that the dialer
transmits as the test signal when the
control panel is in an abnormal state
0 to 9, and A to F
Default: 6F
Periph Trb CODE
Determines the 4/2 code that the dialer
transmits when the control panel and one
or more remote modules are not
communicating
0 to 9, and A to F
Default: 6D
Low Batt CODE
Determines the 4/2 code that the dialer
transmits when the battery voltage is
between 19.4 and 21.4 VDC
0 to 9, and A to F
Default: 6C
Mis Batt CODE
Determines the 4/2 code that the dialer
transmits when the battery voltage is
below 19.4 VDC or the batteries are not
connected
0 to 9, and A to F
Default: 6C
AC Fail CODE
Determines the 4/2 code that the dialer
transmits when the control panel or a
remote auxiliary/booster supply has been
without AC power for longer than the
control panel’s AC fail delay setting
0 to 9, and A to F
Default: 69
Charger CODE
Determines the 4/2 code that the dialer
transmits when the battery charger circuit
can’t adequately charge the batteries
0 to 9, and A to F
Default: 6B
Gnd Flt CODE
Determines the 4/2 code that the dialer
transmits when the control panel detects
an earth ground connection
0 to 9, and A to F
Default: 66
XFMR Tr CODE
Determines the 4/2 code that the dialer
transmits when the expander transformer
in a ten-zone panel is bad or missing
0 to 9, and A to F
Default: 6A
Aux Trb CODE
Determines the 4/2 code that the dialer
transmits when the smoke/accessory
power wiring is shorted
0 to 9, and A to F
Default: 65