Remote module controls and indicators – Edwards Signaling FSC Series User Manual
Page 16
Chapter 1: System overview and operation
8
FSC Series Technical Reference Manual
Remote module controls and indicators
Figure 2: Location of the controls and indicators on the remote modules
Table 5: Descriptions of the remote module controls and indicators
Item Name
Description
1
Power LED
On indicates the control panel has AC power
2
Alarm LED
On indicates an active alarm zone
3 Supervisory
(SUP)
LED
On indicates an active supervisory zone
4
Trouble (TBL) LED
On indicates a system trouble
5
Ground Fault (Gnd
Flt) LED
On indicates a ground fault
6 Silence/Lamp
Test
button
Silences the FSRSI’s buzzer. Pressing this button for more
than 2 seconds activates a lamp test. The lamp test briefly
turns on all FSRI LEDs and all zone indicator module LEDs in
the same peripheral group.
7
Lamp Test LED
On indicates a lamp test is in progress
8
Zone active LEDs
On indicates an active alarm zone. Active supervisory and
monitor zone types, and zone troubles are not indicated.
9
Zone active LEDs
Red indicates an active alarm zone. Yellow indicates an
active supervisory zone. Flashing yellow indicates an active
monitor zone. Zone troubles are not indicated.
1
FSRSI
2
3
4
5
6
7
FSRZI-A
8
FSRZI-SA
9