Edwards Signaling FSC Series User Manual
Page 100
Appendix B: Programming templates
92
FSC Series Technical Reference Manual
IDC 7 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000007
1A EA
Waterflow zone active
None
1
2
1 & 2
(1/3)13000007
2A EA
Trouble
None
1
2
1 & 2
(1/3)37300007
7A FA
Supervisory zone active
None
1
2
1 & 2
(1/3)20000007
3A EA
Monitor zone active
None
1
2
1 & 2
(1/3)40000007
5A EA
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.
IDC 8 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000008
18 E8
Waterflow zone active
None
1
2
1 & 2
(1/3)13000008
28 E8
Trouble
None
1
2
1 & 2
(1/3)37300008
78 F8
Supervisory zone active
None
1
2
1 & 2
(1/3)20000008
38 E8
Monitor zone active
None
1
2
1 & 2
(1/3)40000008
58 E8
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.