Ul 864 programming requirements – Edwards Signaling FSC Series User Manual
Page 34
Chapter 3: Panel programming
26
FSC Series Technical Reference Manual
UL 864 programming requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Programmable
feature or option
Permitted in
UL 864? (Y/N)
Possible
settings
Settings permitted
in UL 864
AC fail delay
Y
0 to 15 hours
1, 2, or 3 hours
Electronic waterflow
retard
Y
0 to 150 seconds
0 to 90 seconds
Nonlatching alarm
circuits
Y No
Yes
No
Yes [1]
NAC wiring class
Y
A
B
Parallel
Yes
Yes
No
Telephone line
supervision duration
Y
0 to 200 seconds
1 to 200 seconds
Telephone line ground
fault supervision
Y No
Yes
Yes
Test signal frequency
Y
0 to 45 days
1 (daily)
Dialer mode
Y
Dual line
Single line
Modem/LCD
LCD only
Dual line
Single line [2]
Modem/LCD [3]
LCD only [3]
Send event restore
codes
Y Send
Restores
No Restores
Send Restores
[1] Allowed only when the IDC is connected to a latching alarm device
[2] Allowed only when the supervising station supervises the telephone line and annunciates fault
conditions within 200 seconds
[3] Prohibited when the control panel is connected to a supervising station