Chapter 4: Dialer programming
50
FSC Series Technical Reference Manual
•
Modem/LCD only:
Dialer is used to communicate with a computer running
the FSCU, and to display text. Dialer functions are disabled.
•
LCD only:
Dialer is only used to display text. Dialer and modem functions are
disabled.
If Single-Line DACT is selected, dual-line programming is skipped. If
Modem/LCD only is selected, all account and receiver related programming is
skipped. If LCD only is selected, all account, receiver, and telephone related
programming is skipped.
To select a dialer mode:
1. Select the Dialer Mode option.
2. Enter a mode.
Setting account options
Table 15 and Table 16 list the set of options for account 1 and account 2 and
their default values.
Review Table 15 and Table 16 and change values as required. If you don’t need
to change any values, go to “Setting dialer options“ on page 51.
Table 15: Account 1 options
Option Description
Values
RCVR1 Phone 1
Account 1’s first telephone number
0 to 9, A, B, asterisk (*), pound
sign (#), and comma (,) up to
20 characters
Default: Blank
RCVR1 Phone 2
Account 1’s second telephone number
0 to 9, A, B, asterisk (*), pound
sign (#), and comma (,) up to
20 characters
Default: Blank
RCVR1 Acct Code Account 1’s identification number
0 to 9, and A to F
Default: FFFF
Alarm Format 1
Determines the format of event codes sent
to account 1
Contact ID or EST 4x2
Default: Contact ID
Restore Type 1
Determines if event restoration codes are
sent to account 1
Send Restores or No Restores
Default: Send Restores