Getting started, When you finish, Restoring panel default settings – Edwards Signaling FSC Series User Manual
Page 37: Enabling passcode protection, Changing the passcode
Chapter 3: Panel programming
FSC Series Technical Reference Manual
29
When you finish
After you have finished programming, make sure the panel is not in a trouble
fault state. No trouble LEDs should be turned on. Test all circuits and panel
functions to make sure that the panel is programmed correctly.
Getting started
Restoring panel default settings
Caution:
Restoring panel default settings disables passcode protection. If you
want passcode protection you must enable it again.
Note:
Restoring panel default settings doesn’t change the passcode and doesn’t
restore dialer default settings.
Control panels are shipped from the factory with default settings for a typical
system. Use the Load Defaults option to restore the panel default settings.
To restore panel default settings:
1. Select the Load Defaults option.
2. Enter Yes.
Enabling passcode protection
Passcode protection prevents unauthorized access to the panel’s programming.
The default passcode is 1111.
This option is only available when a dialer is installed.
To enable passcode protection:
1. Select the Enable Passcode option.
2. Enter Yes.
Changing the passcode
After enabling the passcode, you should change it at your earliest convenience.
Write down the new passcode and store it in a safe place.
This option is only available when a dialer is installed and the passcode is
enabled.