Edwards Signaling FSC Series User Manual
Page 96

Appendix B: Programming templates
88
FSC Series Technical Reference Manual
System events
 
Event 
 
Account 
Contact ID 
event code 
4/2 event 
act. code 
4/2 event 
rest. code 
Test-normal
None 
1
 2  1 & 2
(1/3)60200000
DF 6F
Test-abnormal
None 
1
 2  1 & 2
(1/3)60800000
6F DF
Walk test
None 
1
 2  1 & 2
(1/3)60700000
AF BF
Drill
None
 1  2  1 & 2
(1/3)60100000
AD BD
Reset
None 
1
 2  1 & 2
(1/3)30500000
AB BB
Program mode
None 
1
 2  1 & 2
(1/3)62700000
C1 C2
Dialer disabled
None 
1
 2  1 & 2
(1/3)55100000
AE BE
Panel silence
None
 1  2  1 & 2
(1/3)31500000
CA CA
Signal silence
None
 1  2  1 & 2
(1/3)32800000
AC BC
Ground fault
None 
1
 2  1 & 2
(1/3)31000000
66
D6
Low battery
None 
1
 2  1 & 2
(1/3)30200000
6C DC
Missing battery
None 
1
 2  1 & 2
(1/3)31100000
6C DC
Internal comm. trouble
None 
1
 2  1 & 2
(1/3)30800000
AA BA
AC fail
None 
1
 2  1 & 2
(1/3)30100000
69
D9
Battery charger trouble
None 
1
 2  1 & 2
(1/3)30900000
6B DB
Transformer 2 trouble
None 
1
 2  1 & 2
(1/3)30100000
6A DA
AUX power trouble
None 
1
 2  1 & 2
(1/3)31200000
65
D5
Peripheral trouble
None 
1
 2  1 & 2
(1/3)33000000
6D DD
Phone line 1 trouble
None 
1
 2  1 & 2
(1/3)35100000
68
D8
Phone line 2 trouble
None 
1
 2  1 & 2
(1/3)35200000
6E DE
Delivery trouble
None 
1
 2  1 & 2
(1/3)35400000
67
D7
Notes
1. Default values are shown in bold. 
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values. 
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations. 