Performing lamp tests, Trouble messages, Panel lamp test – Edwards Signaling FSC Series User Manual
Page 73: Fsrsi, fsrzi-a, and fsrzi-sa lamp test
Chapter 5: Maintenance
FSC Series Technical Reference Manual
65
Performing lamp tests
Panel lamp test
A panel lamp test turns on all the LEDs on the panel and on FSRSI, FSRZI-A,
and FSRZI-SA modules so you can verify their proper operation.
To test panel LEDs:
1. Press and hold the Remote Disconnect and Walk Test buttons
simultaneously.
2. Verify that all LEDs on the panel turn on.
If a dialer is installed, the LCD displays:
DB# xx P:x.yy.zz
D:x.yy.zz
Where:
DB# is the database revision number
P:x.yy.zz is the main panel version
D:x.yy.zz is the F-DACT(F) version
FSRSI, FSRZI-A, and FSRZI-SA lamp test
FSRSI, FSRZI-A, and FSRZI-SA modules can be installed individually or in
groups to create a complete remote annunciator. You can perform a local lamp
test on the FSRSI, FSRZI-A, and FSRZI-SA. An FSRSI is required to initiate this
function.
To test FSRSI and FSRZI-A LEDs:
1. Press and hold the FSRSI Silence button for five seconds.
2. Verify that all LEDs on the FSRSI and FSRZI-A modules turn on.
Trouble messages
Table 24: Possible causes of trouble messages
Message Possible
cause
Peripheral trouble
The panel lost communications with the peripherals.