FSC Series Technical Reference Manual
Receiver compatibility
The F-DACT(F) is listed for use with the receivers shown below.
Table 9: Receiver models and formats
Manufacturer Model
Format
Ademco
685
EST 4/2, Contact ID
FBII
CP220
EST 4/2, Contact ID
Osborne-Hoffman
OH 2000
EST 4/2, Contact ID
Radionics D6500
D6600
EST 4/2
EST 4/2. Contact ID
Silent Knight
9000
EST 4/2
Sur-Gard
MLR1, MLR2, MCDI TLR,
TLR+
EST 4/2, Contact ID
Note:
EST 4/2 is SIA DCS-02 P3 with the ability to transmit hexadecimal event codes.
Connecting an auxiliary/booster power
supply
The control panel can provide up to 0.5 A of AUX power to operate ancillary
equipment. For example, remote modules and graphic annunciator cards. If more
than 0.5 A is required, you must use a power-limited and regulated 24 VDC
auxiliary/booster power supply that is UL/ULC Listed for fire protective signaling
systems to power all or some of the ancillary equipment.
Connect an auxiliary/booster supply to the control panel as shown in Figure 7.