Entering values for panel options – Edwards Signaling FSC Series User Manual
Page 36
Chapter 3: Panel programming
28
FSC Series Technical Reference Manual
If you have a dialer, the selected option is displayed on the first line of the LCD. If
not, the option is indicated on the top row of status LEDs.
In the programming instructions that follow, when you see “select the
the option is displayed on the LCD or indicated on the status LEDs.
Entering values for panel options
Use the Panel Silence, Walk Test, and Reset buttons to enter values for the
selected panel option. Pressing the Panel Silence button selects the next value.
Pressing the Walk Test button selects the previous value. Pressing the Reset
button enters the selected value.
If you have a dialer, the selected value is displayed on the second line of the
LCD. If not, the value is indicated on the bottom row of status LEDs.
In the programming instructions that follow, when you see “enter
the Panel Silence or Walk Test buttons until the value is displayed on the LCD or
indicated on the status LEDs then press Reset.
When entering a set of numbers:
1. Press the Panel Silence or Walk Test buttons to increase or decrease the
number.
2. Press the Reset button to enter the number and position the cursor at the
next number.
If the number doesn’t need to be changed, press Reset to go to the next number.
SIGNAL
SILENCE
& DRILL
REMOTE
DISCON-
NECT
NEXT
OPTION
PREVIOUS
OPTION
PANEL
SILENCE
WALK
TEST
NEXT
OPTION
PREVIOUS
OPTION
RESET
ENTER