Chapter 1: System overview and operation
FSC Series Technical Reference Manual
5
Panel controls and indicators
Figure 1: Location of the panel controls, LEDs, and LCD display
Table 4: Descriptions of the panel controls and indicators
Item Name
Description
1
LCD text display
Provides supplemental information relevant to the
current functional condition of the control panel.
Available only when a dialer is installed.
2
System status LEDs
Alarm:
On indicates an active alarm zone.
Trouble:
On indicates a system trouble. For example,
an open, shorted, or disabled circuit, a ground fault, a
battery trouble, an annunciator trouble, or a walk test.
Supervisory (SUP):
On indicates an active supervisory
zone.
Power:
On indicates the control panel has AC power.
Disable:
Double-flashes indicate a disabled IDC, NAC,
remote relay module, or dialer when the control panel is
normal. On indicates a disabled IDC, NAC, remote relay
module, or dialer when the control panel is in alarm.
Waterflow:
On indicates an active waterflow switch.