Setting idc event transmit options – Edwards Signaling FSC Series User Manual
Page 62
Chapter 4: Dialer programming
54
FSC Series Technical Reference Manual
Option Description
Values
Mis Batt Rcvr
Determines where the dialer transmits an
event code when the battery voltage is
below 19.4 VDC or the batteries are not
connected
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Int Comm Tr Rcvr
Determines where the dialer transmits an
event code when the control panel and the
dialer are not communicating
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
AC Fail Rcvr
Determines where the dialer transmits an
event code when the control panel or a
remote auxiliary/booster supply has been
without AC power for longer than the
control panel’s AC fail delay setting
(typically 3 hours)
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Charger Tr Rcvr
Determines where the dialer transmits an
event code when the battery charger
circuit can’t adequately charge the
batteries
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Xfrmr 2 Tr Rcvr
Determines where the dialer transmits an
event code when the expander transformer
in a ten-zone panel is bad or missing
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Aux Pwr Tr Rcvr
Determines where the dialer transmits an
event code when the smoke/accessory
power wiring is shorted
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Periph Trb Rcvr
Determines where the dialer transmits an
event code when the control panel and
one or more remote modules are not
communicating
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Line 1 Trb Rcvr
Determines where the dialer transmits an
event code when the dialer detects a line
cut or ground fault on LINE 1
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Line 2 Trb Rcvr
Determines where the dialer transmits an
event code when the dialer detects a line
cut or ground fault on LINE 2
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Delivery Tr Rcvr
Determines where the dialer transmits an
event code when the dialer transmits a
signal to an account and the account
doesn’t answer
CS 1, CS 2, CS 1 & 2, or None
Default: CS 1
Setting IDC event transmit options
Table 19 lists the set of IDC event transmit options and their default values.