Edwards Signaling FSC Series User Manual
Page 46
Chapter 3: Panel programming
38
FSC Series Technical Reference Manual
IDC Label:
Determines the text displayed on the LCD when the IDC is activated.
The IDC label option is only available when an F-DACT(F) is installed.
Table 12: IDC program options
Step Option
Values
LCD first line
ALARM
TROUBLE
SUP
POWER
DISABLE
LCD second line
WATERFLO
W
ANN TROUBL
E
BATT TROUBLE
GND FAULT
SERVICE DETECTOR
11
IDC Zone Types
Alarm-unverified
(default)
Alarm-verified
WaterFlow-retard
WaterFlow
WF-retard/Supv
WF/Supervisory
Supervisory
Monitor
Remote
SigSil/Drill
Remote
AC
fail
Cross
Zoned
12
IDC Class
Class B (default)
Class
A
13
IDC Non-Latching
No
(default)
Yes
14
IDC Service Chk
No
(default)
Yes
15
IDC RRM Relay [2]
000
(default)
001
002
003
004
005
16
IDC Code Digit 1 [3]
000
(default)