Setting nac 4/2 event activation code options – Edwards Signaling FSC Series User Manual
Page 66

Chapter 4: Dialer programming
58
FSC Series Technical Reference Manual
Table 22: IDC 4/2 event activation code options
Option Description
Values
IDC Alm CDE
Determines the 4/2 code that the dialer 
transmits when the IDC is activated and 
the IDC is an alarm-verified or alarm-
unverified zone type 
0 to 9, and A to F
Default: 1
to 9 (IDC 1 to 9), and A (IDC 
10) 
IDC WF CDE
Determines the 4/2 code that the dialer 
transmits when the IDC is activated by a 
waterflow switch and the IDC is a 
waterflow, waterflow-retard, waterflow/ 
supervisory, or waterflow-
retard/supervisory zone type 
0 to 9, and A to F
Default: 2
to 9 (IDC 1 to 9), and A (IDC 
10) 
IDC Trb CDE
Determines the 4/2 code that the dialer 
transmits when the IDC wiring is open 
0 to 9, and A to F
Default: 7
to 9 (IDC 1 to 9), and A (IDC 
10) 
IDC Sup CDE
Determines the 4/2 code that the dialer 
transmits when the IDC is activated by a 
supervisory device and the IDC is a 
supervisory, waterflow/ supervisory, or 
waterflow-retard/supervisory zone type 
0 to 9, and A to F
Default: 3
to 9 (IDC 1 to 9), and A (IDC 
10) 
IDC Mon CDE
Determines the 4/2 code that the dialer 
transmits when the IDC is activated and 
the IDC is monitor zone type 
0 to 9, and A to F
Default: 3
to 9 (IDC 1 to 9), and A (IDC 
10) 
Setting NAC 4/2 event activation code
options
Table 23 lists the set of NAC 4/2 event activation code options and their default 
values. 
Review Table 23 and make changes as required.
Table 23: NAC 4/2 event activation codes
Option Description
Values
NAC Trb CDE
Determines the 4/2 code that the dialer 
transmits when the NAC wiring is open or 
shorted 
0 to 9, and A to F
Default: 6
to 4 (NAC 1 to 4) 