Minimum system requirements – Edwards Signaling FSC Series User Manual
Page 11
Chapter 1: System overview and operation
FSC Series Technical Reference Manual
3
Model Description
F-XTR120
NAC power expander transformer for ten-zone, 120 V control panels
F-DACT(F)
Dialer/modem for central station reporting and remote programming
CTM
City tie module for connection to a local energy master box
RPM
Reverse polarity transmitter for signaling alarm, supervisory, and trouble
events off-premises
BC-3
External battery cabinet for 17 Ah and 24 Ah batteries
MFC-A
Cabinet enclosure for control panel accessories
EOL3.6-1.1
One 3.6 kΩ and one 1.1 kΩ end-of-line resistor
EOL47PK7
Pack of seven 4.7 kΩ end-of-line resistors
F-TRIM35(G/R)
Trim ring for gray (G) or red (R) three- and five-zone panels
F-TRIM10(G/R)
Trim ring for gray (G) or red (R) ten-zone panels
FSAT1
Remote annunciator trim plate, white, 1-gang
FSAT2
Remote annunciator trim plate, white, 2-gang
FSAT3
Remote annunciator trim plate, white, 3-gang
FSAT4
Remote annunciator trim plate, white, 4-gang
Minimum system requirements
The following table lists the minimum system requirements for each type of fire
alarm system for which the control panel is listed. See Appendix C for wiring
details.
Table 3: Minimum system requirements for listings
Listing Equipment
needed
Protected Premises (Local) Fire
Alarm System
A control panel with at least one alarm initiating device circuit
programmed to activate at least one notification appliance
circuit, and appropriately sized standby batteries
Auxiliary Fire Alarm System,
Local Energy Type
A control panel with at least one alarm initiating device circuit
programmed to activate a dedicated nonsilenceable notification
appliance circuit connected to a local energy master box,
appropriately sized standby batteries, and a CTM module
Remote Supervising Station
Fire Alarm System
A control panel with at least one alarm initiating device circuit,
appropriately sized standby batteries, and an F-DACT(F)
dialer/modem or an RPM module