Edwards Signaling FSC Series User Manual
Page 101
Appendix B: Programming templates
FSC Series Technical Reference Manual
93
IDC 9 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000009
19 E9
Waterflow zone active
None
1
2
1 & 2
(1/3)13000009
29 E9
Trouble
None
1
2
1 & 2
(1/3)37300009
79 F9
Supervisory zone active
None
1
2
1 & 2
(1/3)20000009
39 E9
Monitor zone active
None
1
2
1 & 2
(1/3)40000009
59 E9
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.
IDC 10 events
Event
Account
Contact ID
event code
4/2 event
act. code
4/2 event
rest. code
Alarm zone active
None
1
2
1 & 2
(1/3)11000010
1A EA
Waterflow zone active
None
1
2
1 & 2
(1/3)13000010
2A EA
Trouble
None
1
2
1 & 2
(1/3)37300010
7A FA
Supervisory zone active
None
1
2
1 & 2
(1/3)20000010
3A EA
Monitor zone active
None
1
2
1 & 2
(1/3)40000010
5A EA
Notes
1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.