Appendix d panel specifications – Edwards Signaling FSC Series User Manual
Page 123
FSC Series Technical Reference Manual
115
Appendix D
Panel specifications
Table 30: Panel specifications
Three-zone
control panel
Five-zone
control panel
Ten-zone
control panel
Initiating device
circuits (IDCs)
Class
B
3
5 3 1 10
8 6 4 2 0
Class
A
0
0 1 2 0 1 2 3 4 5
Notification
appliance circuits
(NACs)
Class
B
2
2 0 4 2 0
Class
A
0
0 1 0 1 2
Power supply
4.25 A total
4.25 A total
4.25 A (expandable to 7.5 A total)
NAC voltage rating
Regulated 24 VFWR
Maximum NAC current
2.0 A each
3.5 A total
2.0 A each
3.5 A total
2.0 A each
3.5 A total, 7.0 A with optional
power expander transformer
AC input 120 V, 60 Hz
1.2 A
1.25 A
2.2 A (includes optional power
expander transformer)
Base panel current draw
(standby)
96 mA
104 mA
128 mA
Base panel current draw
(alarm)
180 mA
224 mA
242 mA
Battery placement
Up to two 7 Ah batteries will fit in the
control panel. Use a BC-3 battery
cabinet to install batteries larger than 7
Ah.
Up to two 18 Ah batteries will fit in
the control panel. Use a BC-3
battery cabinet to install batteries
larger than 18 Ah.
Maximum auxiliary current
0.5 amps
Auxiliary output
24 VDC, Regulated
IDC max. detector standby
current
3.0 mA per circuit. See compatibility list P/N 3101019 for a list of approved
detector models and quantities
IDC circuit
Maximum loop resistance: 26 Ω
Maximum loop capacitance: 0.03 µF