Detecting remote modules – Edwards Signaling FSC Series User Manual
Page 38
Chapter 3: Panel programming
30
FSC Series Technical Reference Manual
To change the passcode:
1. Select the Edit Passcode option.
2. Enter the new passcode.
A passcode consists of four characters. Valid characters are the numbers 0 to
9 and the letters A to F.
Detecting remote modules
Use the Find Peripherals option to detect which remote modules are connected
to the control panel when you first configure the control panel and anytime you
add or remove remote modules from the system.
Note:
Do not remove the jumper on J3 (PRG) until the control panel has
completed the detection process. If you do, you must remove all power from the
panel before you can enter local programming mode again.
To detect remote modules:
1. Select the Find Peripherals option.
2. Enter Yes.
The bottom status LEDs will flash until the control panel has completed the
detection process. This may take up to 40 seconds. When finished, the
control panel displays how many remote modules were detected, as shown in
Table 10.
Table 10: Find Peripherals results
Step Option
Values
LCD first line
ALARM
TROUBLE
SUP
POWER
DISABLE
LCD second line
WATERFLO
W
ANN TROUBL
E
BATT TROUBLE
GND FAULT
SERVICE DETECTOR
9
Find Peripherals
was XX now 00
was XX now 01
was XX now 02
was XX now 03
was XX now 04