beautypg.com

Real time clock menu – Watlow EZ-ZONE PM PID User Manual

Page 71

background image

Watlow EZ-ZONE

®

PM PID Controller

68

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[Ad;M]
[Ad.M]

Communications (1)

Modbus Address

Set the network address

of this controller. Each de-

vice on the network must

have a unique address.

1 to 247

1

Instance 1
Map 1 Map 2

2482

2962

0x96 (150)

1

2

- - - -

17007

uint
RWE

[bAUd]
[bAUd]

Communications (1)

Baud Rate

Set the speed of this con-

troller's communications

to match the speed of the

Modbus serial network.

[9600]

9,600 (188)

[`19;2]

19,200 (189)

[`38;4]

38,400 (190)

9,600

Instance 1
Map 1 Map 2

2484

2964

0x96 (150)

1

3

- - - -

17002

uint
RWE

[`PAr]
[ PAr]

Communications

Parity (1)

Set the parity of this con-

troller to match the par-

ity of the Modbus serial

network.

[none]

None (61)

[EuEn]

Even (191)

[`odd]

Odd (192)

None

Instance 1
Map 1 Map 2

2486

2966

0x96 (150)

1

4

- - - -

17003

uint
RWE

[`C_f]
[ C_F]

Communications (1)

Display Units

Select whether this com-

munications channel

will display in Celsius or

Fahrenheit.

Note:

Applies to Modbus only.

[```f]

Fahrenheit (30)

[```C]

Celsius (15)

F

Instance 1

Map 1 Map 2

2490

2970

0x96 (150)

1

6

- - - -

17050

uint

RWE

[M;hL]
[M.hL]

Communications (1)

Modbus Word Order

Select the word order of

the two 16-bit words in

the floating-point values.

[Lohi]

Low-High (1331)

[hiLo]

High-Low (1330)

Low-High Instance 1

Map 1 Map 2

2488

2968

0x96 (150)

1

5

- - - -

17043

uint
RWE

[Map]
[ Map]

Communications (1)

Data Map

If set to 1 the control will

use PM legacy mapping.

If set to 2 the control will

use new mapping to ac-

commodate new functions.

1 to 2

If 9

th

dig-

it of part

number

is a 1, 2,

3 or D.

- - - -

- - - -

- - - -

17059

- - - -

[`nU;S]
[ nV.S]

Communications (1)

Non-Volatile Save

If set to Yes all values

written to the control will

be saved in EEPROM.

[`yes]

Yes (106)

[``no]

No (59)

Yes

Instance 1
Map 1 Map 2

2494

2974

0x96 (150)

1

8

198

17051

uint
RWE

[rtC]

(Available with PM4, PM8 and PM9 models only)

[`SEt]
Real Time Clock Menu

[hoUr]
[hoUr]

Real Time Clock

Hours

Set the current time.

0 to 23

0

Instance 1
Map 1 Map 2

- - - -

4004

88 (136)

1

3

- - - -

36003

uint
RW

Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.

R: Read

W: Write

E:

EE-

PROM

S:

User

Set

* Available with PM4, PM8 and PM9 models only