Watlow EZ-ZONE

®

PM PID Controller

39

Chapter 5 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default Modbus Rela-

tive Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

No Dis-

play

Monitor (1)

Set Point Active

Read the current active set

point.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

Instance 1

Map 1

Map 2

2172 2652

0x6B (107)

1

7

- - - -

7018

float

R

No Dis-

play

Monitor (1)

Autotune Status

Read the present status of

Autotune.

[`off]

Off (62)

[ts;1p]

Waiting for

cross 1 positive (119)

[ts;1n]

Waiting for

cross 1 negative (120)

[ts;2p]

Waiting for

cross 2 positive (121)

[ts;2n]

Waiting for

cross 2 negative (122)

[ts;3p]

Waiting for

cross 3 positive (123)

[ts;3n]

Waiting for

cross 3 negative (150)

[`mn]

Measuring

maximum peak (151)

[`ma]

Measuring min-

imum peak (152)

[CalC]

Calculating

(153)

[Cplt]

Complete (18)

[``to]

Timeout (118)

Instance 1

Map 1

Map 2

1932 2412

0x97 (151)

1

27

- - - -

8027

uint

R

[Loop]
[oPEr]
Control Loop Menu

[`C;M]
[ C.M]

Control Loop (1)

Control Mode

Select the method that

this loop will use to con-

trol.

[`off]

Off (62)

[AUto]

Auto (10)

[MAn]

Manual (54)

Auto

Instance 1

Map 1 Map 2

1880 2360

0x97 (151)

1

1

63

8001

uint
RWES

[A;tSP]
[A.tSP}

Control Loop (1)

Autotune Set Point

Set the set point that the

autotune will use, as a

percentage of the current

set point.

50.0 to 200.0%

90.0

Instance 1

Map 1 Map 2

1998 2398

0x97 (151)

1

0x14 (20)

- - - -

8025

float
RWES

[`AUt]
[ AUt]

Control Loop (1)

Autotune

Start an autotune. While

the autotune is active, the

Home Page will display
[Attn]

[tUn1]. When the

autotune is complete, the

message will clear auto-

matically.

[``no]

No (59)

[`YES]

Yes (106)

No

Instance 1

Map 1 Map 2

1920 2400

0x97 (151)

1

0x15 (21)

64

8026

uint
RW

[`C;SP]
[ C.SP]

Control Loop (1)

Closed Loop Set Point

Set the set point that the

controller will automati-

cally control to.

Low Set Point to High

Set Point (Setup

Page)

75.0°F

or

units

24.0°C

Instance 1

Map 1 Map 2

2160 2640

0x6B (107)

1

1

49

7001

float
RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.

R: Read

W: Write

E: EE-

PROM

S: User

Set