beautypg.com

Watlow EZ-ZONE PM PID User Manual

Page 114

background image

Watlow EZ-ZONE

®

PM PID Controller

111

Appendix

Detection of and Rules Around Abnormal Sensor Conditions

Inputs

Detection of Abnormal Conditions

Thermocouple
Shorted

No direct detection, Open loop firmware detection.

Open

Yes, Parasitic pull-up

Reversed

Yes, firmware detection

Current Source
Shorted

Range limiting only

Open

Range limiting only

Reversed

Range limiting only

Voltage Source
Open

Range limiting only

Shorted

Range limiting only

Reversed

Range limiting only

RTD
S1 open

Yes, pulled up.

S2 open

Not implemented.

S3 open

Yes, pulled up.

S1 short to S2 Yes, pulled up
S1 short to S3 Yes, pulled down to under range.
S2 shorted to S3 Not implemented, Possible, monitor S2 voltage.
S1 and S2 open Yes, pulled down to under range.
S1 and S3 open Yes, S1 pulled up.

S2 and S3 open Yes pulled up.
Thermistor
S1 open

Yes, pulled up to sensor over range.

S3 open

Yes, pulled up to sensor over range.

S1 short to S3 Yes, pulled down to sensor under range.
S1 and S3 open Yes, S1 pulled up to sensor over range.

Troubleshooting Alarms, Errors and Control Issues (cont .)