Watlow EZ-ZONE

®

PM PID Controller

63

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`A;Lo]
[ A.Lo]

Alarm (1 to 4)

Alarm Low Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

low alarm.

deviation - set the span

of units from the closed

loop set point that will

trigger a low alarm. A

negative set point rep-

resents a value below

closed loop set point. A

positive set point rep-

resents a value above

closed loop set point.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

32.0°F

or units

0.0°C

Instance 1

Map 1 Map 2

1482 1882

Offset to next

instance (Map

1) equals +50

Offset to next

instance (Map

2) equals +60

0x6D

(109)

1 to 4

2

18

9002

float
RWES

[`A;hi]
[ A.hi]

Alarm (1 to 4)

Alarm High Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

high alarm.

deviation - set the span

of units from the closed

loop set point that will

trigger a high alarm.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

300.0°F

or units

150.0°C

Instance 1

Map 1 Map 2

1480 1880

Offset to next

instance (Map

1) equals +50

Offset to next

instance (Map

2) equals +60

0x6D

(109)

1 to 4

1

19

9001

float
RWES

[`A;bL]
[ A.bL]

Alarm (1 to 4)

Alarm Blocking

Select when an alarm will

be blocked. After startup

and/or after the set point

changes, the alarm will be

blocked until the process

value enters the normal

range.

[`oFF]

Off (62)

[`Str]

Startup (88)

[StPt]

Set Point (85)

[both]

Both (13)

Off

Instance 1
Map 1 Map 2

1494 1894

Offset to next

instance (Map

1 equals +50,

for Map 2

equals +60)

0x6D (109)

1 to 4

8

28

9008

uint
RWES

[`A;Si]
[ A.Si]

Alarm (1 to 4)

Silencing

Turn alarm silencing on

to allow the user to dis-

able this alarm.

[`oFF]

Off (62)

[``on]

On (63)

Off

Instance 1
Map 1 Map 2

1490

1890

Offset to next

instance (Map

1 equals +50,

for Map 2

equals +60)

0x6D (109)

1 to 4

6

29

9006

uint
RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.

R: Read

W: Write

E:

EE-

PROM

S:

User

Set