Electrical specifications – Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual
Page 118
Specifications
118
Electrical Specifications
DC Model
AC Model
Power Sup
pl
y
Rated Input Voltage
24 Vdc
100...240 Vac
Input Voltage Limits
19.2...28.8 Vdc
85...264 Vac
Rated Frequency
-
50/60 Hz
Rated Frequency Range
-
47...63 Hz
Voltage Drop
10 ms or less
1 cycle or less (Voltage
drop interval must be 1
second or more)
Power Consumption
17 W or less
100 Vac: 44 VA or less
240 Vac: 58 VA or less
When power is not
supplied to external
devices
12 W or less
100 Vac: 30 VA or less
240 Vac: 44 VA or less
Backlight OFF (Standby
Mode)
7 W or less
100 Vac: 18 VA or less
240 Vac: 29 VA or less
Backlight Dimmed
(Brightness: 20%)
8 W or less
100 Vac: 22 VA or less
240 Vac: 31 VA or less
In-Rush Current
30 A or less
Voltage Endurance
1,000 Vac, 20 mA for 1
minute (between
charging and FG
terminals)
1,500 Vac, 20 mA for 1
minute (between
charging and FG
terminals)
Insulation Resistance
500 Vdc, 10 MΩ or more (between charging and
FG terminals)
- GP4500R - 10.4 Standard HMIs with Rear Mounting Options" GP4400R - 7.5 Standard HMI with Rear Mounting Options" GP4300R - 5.7 Standard HMI with Rear Mount" GP4300M - 5.7 Modular HMI" GP4200M - 3.5 Modular HMI" GP4500 - 10.4 W Model HMI" GP4400 - 7.0 W Model HMI" GP4300 - 5.7 W Model HMI" GP4200 - 3.5 W Model HMI" GP4600 - 12.1 Standard HMIs" GP4500 - 10.4 Standard HMIs" GP4400 - 7.5 Standard HMI" GP4300 - 5.7 Standard HMI" GP4200 - 3.5 Standard HMIs"