Structural Specifications
NOTE:
z
If you are using the rear mount model, refer to Structural Specifications (see page
182)
.
NOTE:
*1
The front face of the GP unit, installed in a solid panel, has been tested
using conditions equivalent to the standards shown in the specification. Even though
the GP unit’s level of resistance is equivalent to these standards, oils that should
have no effect on the GP unit can possibly harm the panel. This can occur in areas
where either vaporized oils are present, or where low viscosity cutting oils are
allowed to adhere to the GP unit for long periods of time. If the GP unit’s front face
protection sheet peels off, these conditions can lead to the ingress of oil into the GP
unit and separate protection measures are suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of
the front GP unit’s plastic cover. Therefore, prior to installing the GP unit, be sure to
confirm the type of conditions that will be present in the GP unit’ operating
environment. If the installation gasket is used for a long period of time, or if the GP
unit and its gasket are removed from the panel, the original level of protection cannot
be kept. To maintain the original protection level, be sure to replace the installation
gasket regularly.
*2
For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in.) and R in angle are
below R3 (R0.12 in.)
*3
Even if the installation wall thickness is within the recommended range for the
“Panel Cut Dimensions”, depending on wall’s material, size, and installation location
of the GP unit and other devices, the installation wall could warp. To prevent
warping, the installation surface may need to be strengthened.
GP-4501T / GP-4503T
GP-4501TW
Grounding
Functional grounding: Grounding resistance of 100Ω,
2mm
2
(AWG 14) or thicker wire, or your country’s
applicable standard. (Same for FG and SG terminals)
Cooling Method
Natural air circulation
Structure
*1
IP65F NEMA #250 TYPE 4X/13 (on the front panel
when properly installed in an enclosure)
External Dimensions
W272.5 x H214.5 x D57
mm (W10.73 x H8.44 x
D2.24 in.)
W315 x H241 x D56 mm
(W12.4 x H9.49 x D2.2 in.)
Panel Cut Dimensions
W259 x H201 mm (W10.2
x H7.91 in.)
*2
Panel thickness area:
1.6...5 mm (0.06...0.2
in.)
*3
W301.5 x H227.5 mm
(W11.87 x H8.96 in.)
*2
Panel thickness area:
1.6...5 mm (0.06...0.2
in.)
*3
Weight
2.0 kg (4.4 lb) or less
(main unit only)
2.5 kg (5.5 lb) or less
(main unit only)
CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.
- GP4500R - 10.4 Standard HMIs with Rear Mounting Options" GP4400R - 7.5 Standard HMI with Rear Mounting Options" GP4300R - 5.7 Standard HMI with Rear Mount" GP4300M - 5.7 Modular HMI" GP4200M - 3.5 Modular HMI" GP4500 - 10.4 W Model HMI" GP4400 - 7.0 W Model HMI" GP4300 - 5.7 W Model HMI" GP4200 - 3.5 W Model HMI" GP4600 - 12.1 Standard HMIs" GP4500 - 10.4 Standard HMIs" GP4400 - 7.5 Standard HMI" GP4300 - 5.7 Standard HMI" GP4200 - 3.5 Standard HMIs"