Specifications of serial interface com2, Danger, Caution – Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual
Page 107: 96 5 1 (gp unit side)
GP4000 Series Hardware Manual
107
Specifications of Serial Interface COM2
Introduction
NOTE:
For instructions on how to connect to other devices, always refer to the “GP-
Pro EX Device/PLC Connection Manual”.
The COM2 ports of GP-4501T and GP-4501TW are not isolated. The SG (signal
ground) and FG (frame ground) terminals are connected inside the GP unit.
Serial Interface COM2
GP-4501T / GP-4501TW: D-Sub 9 pin plug connector via an RS-422/485 cable.
Interfit bracket is #4-40 (UNC).
Recommendations:
z
Cable Connector: XM2D-0901 manufactured by OMRON Corporation.
z
Cable Cover: XM2S-0913 manufactured by OMRON Corporation.
z
Jack Screw (#4-40 UNC): XM2Z-0073 manufactured by OMRON Corporation.
DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
z
Verify that a short-circuit loop is not created when you set up the system.
z
Connect the #5 SG terminal to remote equipment when the host (PLC) unit is
not isolated. Connect the #5 SG terminal to a known reliable ground connection
to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.
Pin Connection
Pin
No.
RS-422/RS-485
Signal Name
Direction
Meaning
1
RDA
Input
Receive Data A (+)
2
RDB
Input
Receive Data B (-)
3
SDA
Output
Send Data A (+)
4
ERA
Output
Data Terminal Ready A (+)
5
SG
-
Signal Ground
6
CSB
Input
Send Possible B (-)
7
SDB
Output
Send Data B (-)
8
CSA
Input
Send Possible A (+)
9
ERB
Output
Data Terminal Ready B (-)
Shell
FG
–
Frame Ground (Common
with SG)
CAUTION
LOSS OF COMMUNICATION
z
All connections to the communication ports must not put excessive stress on the
ports.
z
Securely attach communication cables to the panel wall or cabinet.
z
Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.
9
6
5
1
(GP unit side)
- GP4500R - 10.4 Standard HMIs with Rear Mounting Options" GP4400R - 7.5 Standard HMI with Rear Mounting Options" GP4300R - 5.7 Standard HMI with Rear Mount" GP4300M - 5.7 Modular HMI" GP4200M - 3.5 Modular HMI" GP4500 - 10.4 W Model HMI" GP4400 - 7.0 W Model HMI" GP4300 - 5.7 W Model HMI" GP4200 - 3.5 W Model HMI" GP4600 - 12.1 Standard HMIs" GP4500 - 10.4 Standard HMIs" GP4400 - 7.5 Standard HMI" GP4300 - 5.7 Standard HMI" GP4200 - 3.5 Standard HMIs"