Modbus-tcp – Fairbanks FB2550 DAT SERIES DRIVER ACCESS TERMINAL User Manual
Page 94

Section 4: Input/ Output
2/2013
94
51303 Rev. 1
5.8.4. MODBUS-TCP
MODBUS-TCP
(
30925
)
PROTOCOL
was originally developed in 1978 to
exchange information between devices on the factory floor.
It developed into the standard for exchanging data and communication
MODULE STATUS
information between PLC systems.
– MODBUS-TCP devices communicate over a Serial Network in a
master/slave
(request/response) type relationship.
– Uses either the ASCII (American Standard Code for Information Interchange)
mode
or the RTU (Remote Terminal Unit) mode.
In
the
ASCII MODE
, two eight-bit bytes of data are sent as two ASCII
characters.
– The primary advantage of ASCII mode is the flexibility of the timing sequence.
– Up to a one second interval can occur between character transmissions
without causing communication errors.
In
the
RTU MODE
, data is sent as two four-bit, hexadecimal characters,
providing for higher throughput than in ASCII mode for the same baud rate.
– Modbus Plus communicates using a single twisted pair of wires in one
shielded cable (#18AWG).
– Modbus
Plus
does NOT provide power
on the network.
Maximum of up to 32 Nodes, and up to 64 with a Repeater.
NO.
DESCRIPTION
1 Communication
LED
2
Device Status LED
3 MODBUS-TCP
Interface