Configurationandparameter
settingsforModbusTCP
Access word-wise (only 1 byte is valid):
Each access addresses 8 inputs. This results in an address offset of 1 per 8 inputs and an address offset of 4 per
RIO participant.
Main terminal:
257-260
RIO 1
261-264
…
RIO 8
289-292
18.5.3. Configuration data
Method
Data type
Service
Code
Access
Word-wise
Outputs
Write Single Register 06
Write
Word-wise
Inputs
Read Holding Register 03
Read
Access word-wise (only 1 byte is valid):
Each access addresses 8 valves. This results in an address offset of 1 per 8 valves and an address offset of 3 per
RIO participant.
Start address Fault action: 0x201
Main terminal:
513-515
RIO 1
516-518
…
RIO 8
537-539
Start address Fault value: 0x301
Main terminal:
769-571
RIO 1
772-774
…
RIO 8
793-795
Service Parameter
Method
Data type
Service
Code
Access
Word-wise
Outputs
Write Single Register
06
Write
Word-wise
Inputs
Read Holding Register
03
Read
Word-wise
Outputs/Coils
Write Multiple Register
16
Write
Start Device Parameter: 0x401
Object
Length
Data type
Start address
Identification number 6 bytes
String
0x401
Serial number
4 bytes
UINT32
0x404
Input mode
1 bytes
UINT8 (only 1 byte is valid) 0x406
Input filter
1 bytes
UINT8 (only 1 byte is valid) 0x407
english
Type 8640