Pin 2 of the power supply must be supplied with a 4 A medium time-lag fuse; Pin 4 with 1 A.

NOTE!

To ensure electromagnetic compatibility (EMC) connect the screw terminal FE (functional earth) to earth
potential using a short cable (30 cm).

11.1.2. IP20 field bus connection

For connecting the field bus a 9-pole D-SUB connection is used with the following pin assignment (plug in device,
socket on cable).

Pin No.

Signal name

1

not used

2

CAN LOW

3

GND

4

not used

5

not used

6

not used

7

CAN HIGH

8

not used

9

not used

11.1.3. IP20 terminating circuit

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct. The circuit pre-
vents the occurrence of interference caused by signal reflection in the data lines. The trunk line must be terminated
at both ends with resistors of 120 Ω each and 1/4 W power loss.

For the IP20 variant a terminal resistance of 120 Ohm between the two bus connections CAN High and
CAN Low can be added using a bridge in the 9-pole D-SUB field bus connection between pin 4 and pin 8.