9.2.3.

Parameterization of the valve terminal with extension
terminal - bytewise composition of the inputs and outputs

The default value for the parameterization of the main terminal is:

• Extension terminal - none (must be adjusted bytewise on RIO)

• Input mode - normal inputs

• Filter - ON

When extension terminals are used the parameterization option extension terminals RIO bytewise must be
selected.

The parameterization can be used to modify the settings selected for the input mode and the filter.

Further, you may set the length of the device-related diagnosis, whereby the long diagnosis only makes sense
when more than four extension terminals are used. The following settings are permitted in the parameter telegram:

User parameter byte 11 User_Prm_Data

Input mode

Input filter OFF

Input filter ON

Input filter OFF

long diagnosis

Input filter ON long

diagnosis

no inputs

05 hex

45 hex

85 hex

C5 hex

normal inputs

15 hex

55 hex

95 hex

D5 hex

shifted inputs

25 hex

65 hex

A5 hex

E5 hex

halved inputs

35 hex

75 hex

B5 hex

F5 hex

For a description of the input modes and the input filter refer to Section "9.3

Input modes".

9.2.4.

Configuration of the valve terminal with extension terminal -
bytewise composition of the inputs and outputs

The settings of the desired configuration, i.e. setting of various identifiers, is generally done with the help of the GSD
file. Up to 18 identifiers (slots) can be assigned. Each extension terminal starts with a new byte in the process image.
For the main terminal and for each extension terminal 2 identifications are used, i.e. for bytewise configuration the
identifications for a single valve terminal must be contiguous. Each valve terminal can be configured with 4 input
bytes and 3 output bytes.

If there are no inputs / outputs present for a valve terminal, the identification 0 (space) must be entered
here.

Manual configuration: If no GSD file is available the configuration must be performed manually. The following
specifications apply:

Bit 7

Bit 6

Bit 5-4

Bit 3-0

Consistency

0 = byte/word
1 = total length

Bytes / Words

0 = bytes
1 = words (2 bytes)

Input / Output

00 = spec. identifier format
01 = input
10 = output
11 = input/output

Length (amount of data)

0000 = 1 byte / word
...
0010 = 3 bytes / words
...
1111 = 16 bytes / words

Configurationandparameter
settingsforPROFIBUSDP

english