15.5. Fault Action and Fault Value

These settings define the state the valves are to assume in case of fault (bus interruption). The values must be
entered as decimal numbers for groups of 8 at a time (byte-wise).

15.5.1. Fault Action

For Fault Action the meanings are as follows:

0: In case of fault the output assumes the value defined by Fault Value.

1: In case of fault the output retains its current state.
Examples

Valves 1–4 are to assume Fault Value; valves 5–8 retain their current state:

Binary: 1 1 1 1 0 0 0 0 => Decimal: 240

Valves 1, 3, 5, 7 are to assume Fault Value; valves 2, 4, 6, 8 retain their current state:

Binary: 1 0 1 0 1 0 1 0 => Decimal: 170

15.5.2. Fault Value

For Fault Value the meanings are as follows:

0: In case of fault the output is not actuated.

1: In case of fault the output is actuated.
Example

Valves 1, 3, 5, 7 are to be actuated; valves 2, 4, 6, 8 are not actuated:

Binary: 0 1 0 1 0 1 0 1 => Decimal: 85

15.6. Web server

Before the EtherNet slave 8640 can be integrated into the EtherNet network, it must be configured by way of a
Web server. To do this, the PC's network card needed for the purpose must first be configured.

15.6.1. Configuration of the PC network card

Set the IP address of the PC network card.

IP address: 192.168.0.xxx

For xxx enter any numeric value except 100
(100 is assigned to the IP address of the EtherNet slaves by default).

Connect the PC to an EtherNet slave by a network cable.