FieldbusmodulesPROFINETIO,
EtherNet/IPandMODBUSTCP
15.2.1. Errors and warnings displayed via FN (Failure Number)
and FS (Failure Select) LEDs
The following table contains errors and warning messages displayed via the FN (Failure Number) and FS
(Failure Select) LEDs.
The error type is indicated by the number of times FN flashes when FS is set to ON.
The error number is indicated by FN flashing when FS is set to OFF.
Number FN
when FS ON
error type
Number FN
when FS OFF
error number
Description
Remedial action
3
Main terminal error
1
No supply voltage for main terminal
outputs
→
Check supply voltage
3
Error accessing EEPROM
→
Replacement of electronics
may be necessary
4
Peripheral terminal error
1
No supply voltage for peripheral terminal
outputs
→
Check supply voltage
2
Complete failure of a peripheral terminal
→
Check peripheral terminal
RIO bus
As soon as the configuration is correct and a master control system is connected, the bus LED switches from red
to green. Differences from the planned Profinet configuration can be found in the ModulDiffBlock. There are no
configuration or parameter-setting telegrams for any other bus systems.
After the error has been rectified the valve terminal must be reset by briefly shutting down the supply
voltage.