Led status display – Burkert Type 8640 User Manual
Page 79
79
FieldbusmodulesPROFINETIO,
EtherNet/IPandMODBUSTCP
15.2. LED status display
BUS_FAULT (BF)
FAILURE_NUMBER (FN)
U_LOGIK_OK (U
l
)
BUS_OK (BO)
FAILURE_SELECT (FS)
U_TREIBER_OK (U
0
)
Figure 53:
LED state display (detail)
Abbre-
viation
Colour
Description
Explanation
BO
green
Bus OK
Bus communication active
BF
red
Bus Fault
Bus fault
FS
yellow
Failure Select
Determines the function of the FN LED:
FS lit up: FN displays fault type
FS not lit up: FN displays failure number
FN
red
Failure Number
The number of flash impulses indicates the fault type or the
failure number depending on whether FS is lit up or not
U
l
green
U LOGIC OK
Voltage for logic supply, inputs and bus interface present
U
0
green
U driver OK
Voltage for outputs present
Normal state
LED
Status
Description
BUS (BO)
ON
Error-free operation of the valve
terminal on
network
BUS (BF)
OFF
FS
OFF
FN
OFF
U
0
ON
U
L
ON
bus fault
LED
Status
Description
Fault cause / remedial action
BUS (BO)
OFF
Signal monitoring time on valve
terminal elapsed without receipt
of signal from master
During operation:
→
Check master (control) and bus cable
During start-up:
→
Check network configuration on master
BUS (BF)
ON
FS
OFF
FN
OFF
U
0
ON
U
L
ON
english
Type 8640