Led status display – Burkert Type 8640 User Manual

Page 79

background image

79

FieldbusmodulesPROFINETIO,

EtherNet/IPandMODBUSTCP

15.2. LED status display

BUS_FAULT (BF)

FAILURE_NUMBER (FN)

U_LOGIK_OK (U

l

)

BUS_OK (BO)

FAILURE_SELECT (FS)

U_TREIBER_OK (U

0

)

Figure 53:

LED state display (detail)

Abbre-

viation

Colour

Description

Explanation

BO

green

Bus OK

Bus communication active

BF

red

Bus Fault

Bus fault

FS

yellow

Failure Select

Determines the function of the FN LED:
FS lit up: FN displays fault type
FS not lit up: FN displays failure number

FN

red

Failure Number

The number of flash impulses indicates the fault type or the
failure number depending on whether FS is lit up or not

U

l

green

U LOGIC OK

Voltage for logic supply, inputs and bus interface present

U

0

green

U driver OK

Voltage for outputs present

Normal state

LED

Status

Description

BUS (BO)

ON

Error-free operation of the valve

terminal on

network

BUS (BF)

OFF

FS

OFF

FN

OFF

U

0

ON

U

L

ON

bus fault

LED

Status

Description

Fault cause / remedial action

BUS (BO)

OFF

Signal monitoring time on valve
terminal elapsed without receipt
of signal from master

During operation:

Check master (control) and bus cable

During start-up:

Check network configuration on master

BUS (BF)

ON

FS

OFF

FN

OFF

U

0

ON

U

L

ON

english

Type 8640