Example 6 - main terminal with 3 extension terminals Main terminal with 3 valves (outputs) and 3
repeaters (inputs), every second repeat signal not taken into account

• PROFIBUS-DP address 9

• Mode: halved inputs

• Input filter active

• RIO interface

DIP switch main terminal

1

2

3

4

5

6

7

8

ON

OFF

OFF

ON

OFF

OFF

OFF

OFF

Extension terminal 0 with 4 valves (outputs) and no repeaters

• Address 0 (extension terminal 0 always has the address 0)

DIP switch extension terminal 0

1

2

3

4

5

6

7

8

9

10

11

12

OFF

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

Extension terminal 1 with 2 valves (outputs) and 4 repeaters (inputs)

• Address 1 (extension terminal 1 always has the address 1)

• Mode: normal input mode

• Input filter active

DIP switch extension terminal 1

1

2

3

4

5

6

7

8

9

10

11

12

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

ON

OFF

ON

OFF

Extension terminal 2 with 3 valves (outputs) and 6 repeaters (inputs), every second repeat signal remains
unprocessed

• Address 2 (extension terminal 2 always has the address 2)

• Mode: halved inputs

• Input filter active

DIP switch extension terminal 2

1

2

3

4

5

6

7

8

9

10

11

12

OFF

ON

OFF

ON

OFF

OFF

ON

OFF

ON

ON

ON

OFF

Parameter diagram

Here only the user parameters (User_Prm_Data) without the 3 DPV1 status bytes are shown. Counting in
brackets starting at zero (most configuration programs only show user parameters). Value in Hex format.

Configurationandparameter
settingsforPROFIBUSDP

english

Type 8640