Burkert Type 8640 User Manual
Page 40
40
Example 6 - main terminal with 3 extension terminals Main terminal with 3 valves (outputs) and 3
repeaters (inputs), every second repeat signal not taken into account
• PROFIBUS-DP address 9
• Mode: halved inputs
• Input filter active
• RIO interface
DIP switch main terminal
1
2
3
4
5
6
7
8
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
Extension terminal 0 with 4 valves (outputs) and no repeaters
• Address 0 (extension terminal 0 always has the address 0)
DIP switch extension terminal 0
1
2
3
4
5
6
7
8
9
10
11
12
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
Extension terminal 1 with 2 valves (outputs) and 4 repeaters (inputs)
• Address 1 (extension terminal 1 always has the address 1)
• Mode: normal input mode
• Input filter active
DIP switch extension terminal 1
1
2
3
4
5
6
7
8
9
10
11
12
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Extension terminal 2 with 3 valves (outputs) and 6 repeaters (inputs), every second repeat signal remains
unprocessed
• Address 2 (extension terminal 2 always has the address 2)
• Mode: halved inputs
• Input filter active
DIP switch extension terminal 2
1
2
3
4
5
6
7
8
9
10
11
12
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
Parameter diagram
Here only the user parameters (User_Prm_Data) without the 3 DPV1 status bytes are shown. Counting in
brackets starting at zero (most configuration programs only show user parameters). Value in Hex format.
Configurationandparameter
settingsforPROFIBUSDP
english
Type 8640