beautypg.com

Burkert Type 8640 User Manual

Page 19

background image

19

FieldbusmodulePROFIBUSDP/V1

NOTE!

To ensure electromagnetic compatibility (EMC) connect the screw terminal FE (functional earth) to earth
potential using a short cable (30 cm).

Accessories

Plug-in connector (No. 918 226) for power supply (supplied).

8.1.2.

IP20 field bus connection

A 9-pole D-SUB connection is used for an IP20 protection class field bus connection. The following shows the
wiring layout according to Standard 19245 Part 1.

Pin-No.

Signal name (socket in device,

plug on cable)

Description

1

n.c.

-

2

n.c.

-

3

RxD/TxD-P

Receive / Send data P

4

CNTR-P (RTS)

Request to send (repeater control

signal)

5

DGND

Data reference potential

6

+5 V

Supply voltage - plus

7

n.c.

-

8

RxD/TxD-N

Receive / Send data N

9

n.c.

-

english

Type 8640