57

FELDBUSmoduleDeviceNet

State of bus status LEDs

LED

Device state

Explanation

Troubleshooting

not lit up

no voltage /
offline

Device is not supplied with voltage

Device has still not ended Duplicate
MAN ID Test (test lasts approx. 2 sec)

Device cannot end Duplicate MAC
ID Test.

Connect other devices, if the device
is the only network participant

Replace device

Check baud rate

Check bus connection

Green

online, communi-
cation master

Normal operating state with estab-
lished connection to the master

Flashes
green

online, not
communication
master

Normal operating state with estab-
lished connection to the master

Flashes
red

Connection
time-out

One or more I/O connections are in
time-out state.

Red

Critical fault

Another device with the same MAC
ID address is in the circuit.

No bus connection due to communi-
cation problems

Check baud rate

Replace device

After voltage is supplied the following function test of the bus status LEDs is carried out:

• BO LED

lights up briefly (green, approx. 1/4 sec.)

• BF LED

lights up briefly (red, approx. 1/4 sec.)

• LEDs

off

No output voltage present:

LED

Status

Remedial action

U

0

FS
FN

OFF

FS and FN display fault type 3 and fault

number 1.

Check supply voltage

EEPROM access fault

LED

Status

Remedial action

FS
FN

FS and FN display fault type 5 and fault

number 1.

Error accessing EEPROM during start-up;

flashing sequence only appears once.

Device operating with default parameters.
Replacement of electronics may be necessary.

english