Programming, Multipump – constant pressure control – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 93

93
MultiPump – Constant Pressure Control
18.
After 2203 has been selected, press the down arrow to
highlight parameter 2204 “SWITCH LEAD LAG”. Press
the EDIT key once. Using the up or down arrows, select
the alternating time between lead and lag pumps. Once
selected, press the SAVE key.
19.
Once 2204 has been saved, press the down arrow to
highlight “2207 PUMP ADDRESS”. Press the EDIT key once.
Use the up arrow to select your appropriate address for
each pump. Always start with address one. Once each
pump has a different address, press the SAVE key.
20. Final step is to enter your required system
pressure. After above programming has been
completed for each Aquavar controlled pump,
press the EXIT key two (2) or three (3) times, until
you arrive back to the first control display screen.
(SEE DIAGRAM.) Then press the UP or DOWN
arrow to select the required system pressure for
your Aquavar controlled pump. Once pressure has
been selected, press the green START key on the
keypad.
21. Optional Step: To lock out access to the control
panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual. When troubleshooting an Aquavar system, always break down into the following
components:
1. Aquavar programming — check default settings recommended for single pump, multi-
pump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical
problems. Pump “ run out”.
4. Hydraulic System/ Piping — check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment — protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
EXIT
EDIT
REM
PARAMETERS
2201 VALUE DECREASE
2202 VALUE INCREASE
2203 ENABLE SEQUENCE
2204 SWITCH LEAD/LAG
12 H
EXIT
EDIT
REM
PARAMETERS
2204 SWITCH LEAD/LAG
2205 SYNC LIMIT
2206 SYNC WINDOW
2207 PUMP ADDRESS
0
PROGRAMMING
DIR
MENU
REM
11.1%
LOC
REM
Status
LED
UP
SOFT
KEY 1
DOWN
LOC/REM
STOP
START
HELP
SOFT
KEY 2
40.2 PSI
sp
0.0 PSI
ac
0.0 HZ