Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 75

75
Single Pump Programming (Pressure transducer)
7. Use the down arrow until group parameter 1105 “MOTOR
NOM CURRENT” is highlighted, then press EDIT. Using
the
arrows, enter your motor’s maximum allowed amp draw at
full
speed, or Service Factor Amps. NOTE: Enter motors service
factor from nameplate or motor manual. Once you have
entered the amps, press the SAVE key.
8. Use down arrow until you highlight group parameter 1107
“MOTOR NOM RPM”, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.
9. Use down arrow until you highlight group parameter 1108
“MOTOR NOM POW”, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.
10. Once you have saved parameter 1108, use the down
arrow until you highlight group parameter 1201 “START/
STOP”, then press EDIT. Default is “KEYPAD”. This parameter
determines how the operator will control the Aquavar; via
the keypad or via MODBUS communication. If no changes
are required, press the CANCEL key then EXIT and go to the
next step.
11. From group 12, press the down arrow until group 14 “SPD
LIM/STRT LVL” is highlighted, then press EDIT. Use down
arrows to highlight group 1402 “MINIMUM FREQ”, then
press EDIT. Using the arrow keys select the appropriate
minimum speed in HZ. Default is 10% of the parameter
1106 MOTOR NOM FREQ which is 6 HZ. For a submersible
motor or suction lift situation, this would be set to at least
30 HZ. For a positive suction booster system, leave at the default setting. Once changed,
press the SAVE key to store the setting.
EXIT
EDIT
REM
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
3.4A
EXIT
EDIT
REM
PARAMETERS
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
3550 RPM
EXIT
EDIT
REM
PARAMETERS
1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
1108 MOTOR NOM POW
1.0 HP
EXIT
EDIT
REM
PARAMETERS
1111 MOTOR ID RUN
1201 START/STOP KEYPAD
1202 AUTO RESTART
1203 TEST RUN
PROGRAMMING
EXIT
EDIT
REM
PARAMETERS
1401 MAXIMUM FREQ
1402 MINIMUM FREQ
30.0 HZ
1403 CONFIG SPEED MIN
1404 STP DELY MIN SPD