Cable Sizing/Ratings
380…480 Volt Drives
The following table provides Aquavar CPC rating information and
recommended wire sizing for the input and output cables.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Frame
Output
Input
Voltage Phase
Base
Load
DUTY
Size
2
Cable Size
Cable Size
Model
Amps
HORSEPOWER
Min. AWG
1
Min. AWG
1
CPC40061 6.9
3
R1
14
14
CPC40081 8.8
5
R1
14
14
CPC40121 11.9
7.5
R1
14
14
CPC40151 15.4
10
R2
12
12
CPC40231 23
15
R2
12
12
CPC40311 31
20
R3
10
8
CPC40381 38
25
R3
8
8
CPC40451 45
30
R3
8
6
CPC40591 59
40
R4
6
4
CPC40721 72
50
R4
4
3
CPC40771 77
60
R4
4
3
460
3 CPC40971 97
75
R4
3
1
CPC41251 125
100
R5
1
2/0
CPC41571 157
125
R6
2/0
3/0
CPC41801 180
150
R6
3/0
4/0
CPC42451 245
200
R7 350MCM 350MCM
CPC43161
316
250
R7
2 X 250MCM 2 X 250MCM
CPC43681
368
300
R8
2 X 300MCM 2 X 300MCM
CPC44141
414
350
R8
2 X 400MCM 2 X 400MCM
CPC44861
486
400
R8
2 X 500MCM 2 X 500MCM
CPC45261
526
450
R8
2 X 350MCM 2 X 350MCM
CPC46021
602
500
R8
2 X 500MCM 2 X 500MCM
CPC46451
645
550
R8
2 X 500MCM 2 X 500MCM
(1) Recommended AWG Size based on NEC table 310.16, 40º C ambient, 90º C, UL type copper wire. For other
wire sizes or types, consult local, state or NEC codes.
(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult
technical section (CABLE TERMINALS) for maximum wire diameter and torque values.