Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 66

66
Defaults
Group
Regulate Range
Description
Single Synch- Multi- Constant Speed
21
Pump ronous Control Slave Control
2102 Press Incr Speed 0…60 Hz
Sets the speed for which
20 20 20 20 20
additional pressure is added to
compensate for system frictional
losses at increased flow. Used for
single pump and backup modes
only. Default = 20 Hz.
2103 Press Incr
0….10000
The pressure increase in selected
0 0 0 0 0
units point which is added to the
set point pressure to compensate
for frictional losses at the pressure
increase speed. Used for single
pump and backup modes only.
Note the full set point pressure
increase (%) is achieved at
maximum speed (1401).
Group Multipump
Range Description
Single Synch- Multi- Constant Speed
22
Control
Pump ronous Control Slave Control
2201 Value Decrease 0…1000
Defines how much the actual
5
5
5
5
5
can drop before the next lag
pump is started. Used for
multicontrol, synchronous
control and slave modes only.
2202 Value Increase
0….1000
Defines the increase in set point
5
5
5
5
5
when a lag pump starts. This
value is cumulative with each
lag pump that turns on. Used
for multicontrol, synchronous
control and slave modes only.
The default setting for 2202 is
equal to the value set in 2201.
2203 Enable Sequence 0… 60 Hz
Defines the speed the drive
59
59
59
59
59
must be at before multipump
operation is allowed.. Applies to
synchronous, multicontrol and
slave modes only. Default =
98% of 1401 Maximum Speed.
2204 Switch Lead Lag 1…100 h
Defines the time the lead unit
48
48
48
48
48
will run before a new unit is
deemed the lead unit. Note if
set to 1001 (Not SEL) the
switching function is disabled
(including switching during a
fault). Default setting is 48 hrs.
PARAMETER LISTINGS