Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 71

71
Defaults
Group
Modbus Range
Description
Single Synch- Multi- Constant Speed
32
Setup
Pump ronous Control Slave Control
3201 Protocol ID
0…0xFFFF
This parameter configures the
module type automatically by
the fieldbus adapter. No action
is required by the user unless
changes to default settings are
desired. Refer to the fieldbus
manual.
3202 Station ID
0...247
1
1
1
1
1
3203 Baud Rate
1.2…57.6
9.6
9.6
9.6
9.6
9.6
kbits/s
kbits/s kbits/s kbits/s
kbits/s kbits/s
3204 Parity
Defines the data length, parity
8N2
8N2
8N2
8N2
8N2
and stop bits.
8N1
8 data bits, no parity and one
stop bit
8N2
8 data bits, no parity and two
stop bits
8E1
8 data bits, even parity and one
stop
bit.
8O1
8 data bits, odd parity and one
stop
bit.
3205 Control
Selects the communication
ABB
ABB
ABB
ABB
ABB
Profile
profile.
Drives Drives
Drives
Drives
Drives
ABB Drives
ABB Drives control word and
Status Word.
AV
Alternate Profile.
3206 OK Messages
0…65535
Read only counter of good
Modbus messages.
3207 CRC Errors
Read only counter of CRC errors.
3208 EFBUART Errors
Read only counter of UART errors.
3209 EFB Status
Contains the status of Modbus
protocol.
Idle
Drive is configured for Modbus,
but not receiving any messages.
Exec. Init
Drive is initializing Modbus.
Time Out
A time-out has occurred .
Config Error
Drive has configuration error.
Off-line
Drive is receiving messages that
are NOT addressed to itself.
On-Line
Drive is receiving messages that
are addressed to itself.
Reset
Drive is performing hardware
reset.
Listen Only
Drive is in listen only mode.
PARAMETER LISTINGS