Faults/alarms, Correcting faults – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 116

116
Correcting Faults
The recommended corrective action for faults is:
• Use the “Fault Listing” table below to find and address the root cause of the problem.
• Reset the drive. See “Fault Resetting” on page 119.
* Drive not ready fault. Check supply voltage / DC Bus = 1.35 x input voltage.
* Comm fault drive not responding. Internal communication lost.
• Cycle Power • Remove and reinstall panel • Replace panel
Fault Listing
Fault Fault Name
Description and Recommended Corrective Action
Code In Panel
1 OVERCURRENT
Output current is excessive. Check for and correct:
• Excessive motor load, pump overload.
• Insufficient acceleration time (parameters 1301 Ramp 1 and 1302 Ramp 2).
• Faulty motor, motor cables or connections.
2 DC OVERVOLT
Intermediate circuit DC voltage is excessive. Check for and correct:
• Static or transient overvoltages in the input power supply.
• Insufficient deceleration time (parameters 1302 Ramp 2, increase to at least
8 seconds).
3 DEV OVERTEMP
Drive heatsink is overheated. Temperature is at or above 115º C (239º F).
Check for and correct:
• Fan failure
• Excessive ambient temperature
• Obstructions in the air flow
• Excessive motor load
• Dirt or dust coating
• Ambient temperature
on the heat sink
• Altitude
4 SHORT CIRC
Fault current. Check for and correct:
• A short-circuit in the motor cable(s) or motor
• Supply disturbances
5 OVERLOAD
Inverter overload condition. The drive output current exceeds the ratings given
in “Ratings” on pages 131-134 of this manual.
6 DC UNDERVOLT
Intermediate circuit DC voltage is not sufficient. Check for and correct:
• Missing phase in the input power supply
• Blown fuse/check input wiring
• Undervoltage on mains
7
AI
1 LOSS
Analog input 1 loss. Analog input value is less than
AI
1
MIN
(1604).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
AI
1
MIN
(1604).
8
AI
2 LOSS
Analog input 2 loss. Analog input value is less than
SENSOR MIN
(1506).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
SENSOR MIN
(1506) and (1503)
TRANSDUCER MIN
.
9 MOT OVERTEMP
Motor is too hot, based on either the drive’s estimate or on temperature
feedback device.
• Check for overloaded motor.
• Adjust the parameters used for the estimate (1104…1109).
• Check the temperature sensors and Group 11 parameters.
• Check motor wiring and connections. Possible MOTOR phase loss.
FAULTS/ALARMS