Faults/alarms – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 118

118
Fault Fault Name
Description and Recommended Corrective Action
Code In Panel
27 CONFIG FILE
Internal configuration file has an error. Contact your local factory
representative.
• Cycle power
• Check Group 9902 / Drive Size Type
28 SERIAL 1 ERR
Fieldbus communication has timed out. Check for and correct:
• Fault setup (2409
COMM FAULT FUNC
and 2410
COMM FAULT TIME
).
• Communication settings (Group 31 or 32 as appropriate).
• Poor connections and/or noise on line.
29 EFB CON FILE
Error in reading the configuration file for the fieldbus adapter.
30 FORCE TRIP
Fault trip forced by the fieldbus. See the fieldbus User’s Manual.
31 EFB 1
Fault code reserved for the EFB protocol application.
32 EFB 2
The meaning is protocol dependent.
33 EFB 3
34 MOTOR PHASE
Fault in the motor circuit. One of the motor phases is lost.
Check for and correct:
• Motor fault
• Motor wiring, connections
• Motor cable fault
• Internal fault
35 OUTP WIRING
Error in power wiring suspected. Check for and correct:
• Input power wired to drive output
• Ground faults
101 SERF CORRUPT
Error internal to the drive. Contact your local factory
102 SERF IITFILE
representative and report the error number.
103 SERF MACRO
104 SERF EFBPROT
105 SERF BPFILE
201 DSP T1 OVERLOAD
Error internal to the drive. Contact your local factory
202 DSP T2 OVERLOAD
representative and report the error number.
203 DSP T3 OVERLOAD
204 DSP STACK ERROR
205 DSP REV ERROR
206 OMIO ID ERROR
Faults that indicate conflicts in the parameter settings are listed below.
1000 PAR HZRPM
Parameter values are inconsistent. Check for any of the following:
• 2001
MINIMUM SPEED
> 2002
MAXIMUM SPEED
.
• 2007
MINIMUM FREQ
> 2008
MAXIMUM FREQ
.
• 2001
MINIMUM SPEED
/ 9908
MOTOR NOM SPEED
> 128 (or < -128).
• 2002
MAXIMUM SPEED
/ 9908
MOTOR NOM SPEED
> 128 (or < -128).
• 2007
MINIMUM FREQ
/ 9907
MOTOR NOM FREQ
> 128 (or < -128).
• 2008
MAXIMUM FREQ
/ 9907
MOTOR NOM FREQ
> 128 (or < -128).
1001 PAR PFCREFNG
Parameter values are inconsistent. Check for the following:
• 2007
MINIMUM FREQ
is negative.
1003 PAR AI SCALE
Parameter values are inconsistent. Check for any of the following:
• 1503
TRANSDUCER
MIN
> 1502
TRANSDUCER
MAX
.
1004 PAR AO SCALE
Parameter values are inconsistent. Check for any of the following:
• 1904
AO
1
MIN
> 1905
AO
1
MAX
.
• 1909
AO
2
MIN
> 1910
AO
2
MAX
.
FAULTS/ALARMS