Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 56

56
Defaults
Group
Start-Up Range
Description
Single Synch- Multi- Constant Speed
11
Data
Pump ronous Control Slave Control
1104 Motor Nom
11…345V/
Defines the motor voltage.
230/ 230/ 230/ 230/ 230/
Voltage
230…690V
Equal to the value on the
460/
460/
460/
460/
460/
motor nameplate.
575 575 575 575 575
1105 Motor Nom
0.2*I
2hd
…
Defines the motor current.
1.0* 1.0* 1.0* 1.0* 1.0*
Current
2.0*I
2hd
Equal to the value on the
I
2hd
I
2hd
I
2hd
I
2hd
I
2hd
motor nameplate.
1106 Motor Nom Freq 10.0…500Hz Defines the motor nominal
60 60 60 60 60
frequency. Equal to the value
on the motor nameplate.
1107 Motor Nom RPM 50…18000
Defines the motor nominal
3550 3550 3550 3550 3550
RPM
speed. Equal to the value on
the motor nameplate.
1108 Motor Nominal 0.2…2.0*P
hd
Defines the motor power (hp). 1.0*P
hd
1.0*P
hd
1.0*P
hd
1.0*P
hd
1.0*P
hd
Power
Equal to the value on the
nameplate.
Group
Start/Stop Range
Description
Single Synch- Multi- Constant Speed
12
Pump ronous Control Slave Control
1201 Start/Stop
Defines the connections and
Keypad Keypad Keypad Keypad Keypad
source of the start/stop
commands.
Comment - DI1 = Enable. 0= Disable,
1 = Enable. DI2 = Low Water. 0 = Fault,
1 = OK, DI3 = Estop 0 = Estop, 1 = OK,
After Estop restart from keypad required.
Keypad
Start/Stop from keypad. After a
fault reset, the drive will restart
only if auto restart (1202) is set
to on. If auto restart is off the
drive must be started from the
keypad.
Fieldbus
Start via fieldbus control word
1202 Auto Restart
Selects whether the AV will
On On On On On
automatically restart after a
power failure or fault reset.
Off
Not selected
On
Selected. The AV will automatic-
ally restart if conditions permit.
1203 Test Run
Selects when the drive will
Not Sel Not Sel Not Sel Not Sel Not Sel
perform a test run
Not Sel (default) Not selected
PARAMETER LISTINGS