Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 64

64
Defaults
Group
Relay Range Description
Single Synch- Multi- Constant Speed
18
Outputs
Pump ronous Control Slave Control
Low Water
The secondary protection
warning or fault function has
been activated. DI4 is low for
the protection delay setting
(2404). Closed = normal,
Open = Secondary Protect fault
function is active.
Pump Protect The pump protection warning or
fault function has been activated.
Start Slave
Used in multipump macro to
start slave pump only.
Stand by
Drive is in sleep mode due to
no system demand.
1808 RO3 ON Delay
0…3600 s
Defines the operation delay for
0
0
0
0
0
relay output RO3.
1809 RO3 OFF Delay 0… 3600 s
Defines the release delay for
0
0
0
0
0
relay output RO3.
Group
Analog
Range Description
Single Synch- Multi- Constant Speed
19
Outputs
Pump ronous Control Slave Control
1901 AO 1 Content Sel
Connects a AV signal to analog Not
Not
Not
Not
Not
output 1 (AO1).
Used
Used
Used
Used
Used
Not Sel (default) Not in use.
Frequency
Output frequency. 20 mA =
motor nominal frequency (1106).
Current
Output current. 20 mA =
motor nominal current (1105).
Torque
Motor torque. 20 mA = 100%
of motor nominal rating.
Power
Motor Power. 20 mA = 100%
of motor power rating.
Proc Var/
Actual value of process variable
Actual
AI2. 20 mA = Reference 1 Max
(1603).
Energy Saving Calculated energy savings
(option 1 or 2) over a conven-
tional fixed speed system.
20 mA = Savings scale (2603).
1902 AO1 Content
Various
Selects the minimum value of the
Min
characterisitc being monitored.
1903 AO1 Content
Various
Selects the maximum value of the
4
4
4
4
4
Max
characteristic being monitored.
PARAMETER LISTINGS